PERMIT SEARCH PORTAL
Details

Identification

Permit Number
BLD202510535
Type
Electrical - Electrical
Added On
07-25-2025 07:29 AM
Declared Value
$12,900.00


Status (Finalized)

Expires On
06-03-2026
Issued On
07-30-2025
Final On
12-05-2025
Certified On


Description of Work

USE BLD202510535-03

USE BLD202510535-02
USE BLD202510535-01
installing a roof mounted solar PV system / NOC FOR SOLAR INSTALLATION ON ROOF IN OR BK:3517 PG:417/ RECORDED NOC MUST BE ON SITE IN PERMIT PACKAGE FOR INSPECTOR REVIEW

Please complete the solar attachment affidavit and re-submit once installation is completed.



Site Information

Primary Address
6656 W HILGER CT HOMOSASSA, FL 34448
Other Linked
1719130020000000230 SINGING TREES
19
17
13
00000
0230


Contacts

Contacts

Licensed Contact Primary AFFORDABLE SOLAR ROOF & AIR 4914 CREEKSIDE DRIVE, SUITE A CLEARWATER, FL 33760

Property Owner RINELLA GREGORY GEORGE AND ROXANNE LYNN 6656 W HILGER CT HOMOSASSA, FL 34448



Related

Building Permits

Child BLD202510535-03 Amendment 11-19-2025 Closed

Child BLD202510535-02 Amendment 10-28-2025 Closed

Child BLD202510535-01 Amendment 08-27-2025 Closed



Progress

Reviews
Permit Specialist Review Approved

Electrical Plan Review Approved

Building Plan Review Approved
| Assigned to Reviewer: Stephen R Switzer stephen.switzer@citrusbocc.com |
Review Consolidation Approved
| Assigned to Reviewer: Shannon Lutton shannon.lutton@citrusbocc.com |
Pre Permit Issuance Review Add Fees
| Assigned to Reviewer: Shannon Lutton shannon.lutton@citrusbocc.com |
Pre Permit Issuance Review Approved
| Assigned to Reviewer: Shannon Lutton shannon.lutton@citrusbocc.com |
NOC Review Approved
| Assigned to Reviewer: Shannon Lutton shannon.lutton@citrusbocc.com |

Conditions

Inspections
Final Electric Inspection (#1)Scheduled For: 10-03-2025Is Assigned Failed on 10-03-2025
| Assigned to Inspector: Joe Moss |
Violations

10-03-2025See Violation Details in Comments Transferred to Re-inspection10-03-2025
Not per plans r107.4 not per county approved construction documents 100 percent reinspection when county approves plan revisions. below is a list to help at next inspection, not a full list of needed corrections. 1. need to revise plan to reflect all panels, and disconnects installed. and correct locations. 2. plan shows 30 amp breaker , line taps have been used instead. 3. earth grounding is not per plans. 4. generator components have been added that are not on the plan.

Final Electric Inspection (#2)Scheduled For: 11-10-2025Is Assigned Failed on 11-10-2025
| Assigned to Inspector: Jeremy Lentz |
Violations

10-03-2025See Violation Details in Comments Transferred to Re-inspection11-10-2025
Not per plans r107.4 not per county approved construction documents 100 percent reinspection when county approves plan revisions. below is a list to help at next inspection, not a full list of needed corrections. 1. need to revise plan to reflect all panels, and disconnects installed. and correct locations. 2. plan shows 30 amp breaker , line taps have been used instead. 3. earth grounding is not per plans. 4. generator components have been added that are not on the plan.

11-10-20252nd Fail Same Reason Transferred to Re-inspection11-10-2025
Not to Plan. Install must match plan Plans show 30amp back fed breaker and non-fused disconnect. Line side tap and unfused disconnect installed. If line side tap is installed the disconnect must be fused. R.V. panel installed and not on plans.

Final Electric Inspection (#3)Scheduled For: 12-05-2025Is Assigned Passed on 12-05-2025
| Assigned to Inspector: Jeremy Lentz |
Violations

10-03-2025See Violation Details in Comments Complied12-05-2025
Not per plans r107.4 not per county approved construction documents 100 percent reinspection when county approves plan revisions. below is a list to help at next inspection, not a full list of needed corrections. 1. need to revise plan to reflect all panels, and disconnects installed. and correct locations. 2. plan shows 30 amp breaker , line taps have been used instead. 3. earth grounding is not per plans. 4. generator components have been added that are not on the plan.

11-10-20252nd Fail Same Reason Complied12-05-2025
Not to Plan. Install must match plan Plans show 30amp back fed breaker and non-fused disconnect. Line side tap and unfused disconnect installed. If line side tap is installed the disconnect must be fused. R.V. panel installed and not on plans.

Final Power Release (#1)Scheduled For: 12-05-2025Is Assigned Confirmed on 12-05-2025
BLD202510535 Owner Name: RINELLA GREGORY GEORGE AND RINELLA ROXANNE LYNN Inspection Passed on: 12/5/2025 is for Photovoltaic
Engineers Inspection Affidavit (#1)Scheduled For: 09-30-2025 Approved on 09-30-2025