PERMIT SEARCH PORTAL
Details

Identification

Permit Number
BLD202505958
Type
Electrical - Electrical
Added On
04-23-2025 01:16 PM
Declared Value
$2,006.00


Status (Finalized)

Expires On
12-16-2025
Issued On
05-05-2025
Final On
06-20-2025
Certified On


Description of Work

 Install 30 amp circuit from panel to Nema 6 enclosed control box continue circuit to lift station enclosure. Septic to Sewer Conversion. **LIFT STATION Permit BLD202504823 ** HURRICANE STORM DAMAGE PERMIT# BLD202501958 ** NOC N/A ** **FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - CONTROL BOX BELOW DFE TO UTILIZE NEMA 6 ENCLOSURE - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) *



Site Information

Primary Address
3748 N HIAWATHA TER CRYSTAL RIVER, FL 34428
Other Linked
1718170220000D00280 INDIAN WATERS UNIT 2
18
17
17
000D0
0280
17181700004A0D00290 UNREC TRACTS IN 17-18S-17E
18
17
17
4A0D0
0029


Contacts

Contacts

Licensed Contact Primary MORGAN ELECTRIC LLC P.O. BOX 161 CRYSTAL RIVER, FL 34423

Property Owner RANDY A & MARCIA SAMUELSON 3748 N HIAWATHA TER CRYSTAL RIVER, FL 34428



Related

Building Permits

Parent BLD202504823 Plumbing/Irrigation/Solar Type 04-03-2025 Finalized

Parent BLD202501958 Addition/Renovation 02-09-2025 Issued



Progress

Reviews
Permit Specialist Review Approved

Flood Review Request for Information
<div>FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - ELECTRIC MUST MEET BFE: 10.0', EXISTING GRADE APPROX: 4.0' - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) - MISSING ALL FLOOD HAZARD INFORMATION - MISSING ELECTRIC STATEMENT AND&nbsp;ELEVATIONS<b>&nbsp;- WHAT IS THE ELEVATION OF THE BOTTOM OF THE SERVICE PANEL?</b></div><div><ol><li>FLOOD ZONE WHERE THE PROPOSED STRUCTURE WILL BE LOCATED MUST BE SPECIFIED (CCCO SEC 18-193 - FBC R322.2, R322.3 - DETERMINES REQUIREMENTS)</li><li>BFE &amp; DFE ELEVATIONS MUST BE STATED AND SHOWN ON ELEVATION PAGES (CCCO SEC 18-193 - FBC R322.1, R322.1.4.1)</li><li>STATEMENT IS REQUIRED THAT ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS TO BE AT OR ABOVE DFE (CCCO SEC 18-193 - FBC R322.1.6, FEMA P-348, PAGES 3-8)&nbsp;</li><li>ALL MATERIAL BELOW DFE MUST BE FLOOD RESISTANT AND CONFORM TO THE PROVISIONS OF FEMA TB-2(CCCO SEC 18-193 - FBC R322.1.8)</li></ol></div>
Additional Information

04-28-2025Flood Misc.
<div>FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - ELECTRIC MUST MEET BFE: 10.0', EXISTING GRADE APPROX: 4.0' - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) - MISSING ALL FLOOD HAZARD INFORMATION - MISSING ELECTRIC STATEMENT AND&nbsp;ELEVATIONS<b>&nbsp;- WHAT IS THE ELEVATION OF THE BOTTOM OF THE SERVICE PANEL?</b></div><div><ol><li>FLOOD ZONE WHERE THE PROPOSED STRUCTURE WILL BE LOCATED MUST BE SPECIFIED (CCCO SEC 18-193 - FBC R322.2, R322.3 - DETERMINES REQUIREMENTS)</li><li>BFE &amp; DFE ELEVATIONS MUST BE STATED AND SHOWN ON ELEVATION PAGES (CCCO SEC 18-193 - FBC R322.1, R322.1.4.1)</li><li>STATEMENT IS REQUIRED THAT ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS TO BE AT OR ABOVE DFE (CCCO SEC 18-193 - FBC R322.1.6, FEMA P-348, PAGES 3-8)&nbsp;</li><li>ALL MATERIAL BELOW DFE MUST BE FLOOD RESISTANT AND CONFORM TO THE PROVISIONS OF FEMA TB-2(CCCO SEC 18-193 - FBC R322.1.8)</li></ol></div>

Electrical Plan Review Request for Information

Additional Information

04-29-2025SEE PROBLEM DETAILS IN COMMENTS
<div>LOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - ELECTRIC MUST MEET BFE: 10.0', EXISTING GRADE APPROX: 4.0' - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) - MISSING ALL FLOOD HAZARD INFORMATION - MISSING ELECTRIC STATEMENT AND&nbsp;ELEVATIONS<b>&nbsp;- WHAT IS THE ELEVATION OF THE BOTTOM OF THE SERVICE PANEL?</b></div><div><ol><li>FLOOD ZONE WHERE THE PROPOSED STRUCTURE WILL BE LOCATED MUST BE SPECIFIED (CCCO SEC 18-193 - FBC R322.2, R322.3 - DETERMINES REQUIREMENTS)</li><li>BFE &amp; DFE ELEVATIONS MUST BE STATED AND SHOWN ON ELEVATION PAGES (CCCO SEC 18-193 - FBC R322.1, R322.1.4.1)</li><li>STATEMENT IS REQUIRED THAT ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS TO BE AT OR ABOVE DFE (CCCO SEC 18-193 - FBC R322.1.6, FEMA P-348, PAGES 3-8)&nbsp;</li><li>ALL MATERIAL BELOW DFE MUST BE FLOOD RESISTANT AND CONFORM TO THE PROVISIONS OF FEMA TB-2(CCCO SEC 18-193 - FBC R322.1.8)</li></ol></div>

Review Consolidation Request for Information
<b><u>FLOOD DENIED:</u></b><div><div>FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - ELECTRIC MUST MEET BFE: 10.0', EXISTING GRADE APPROX: 4.0' - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) - MISSING ALL FLOOD HAZARD INFORMATION - MISSING ELECTRIC STATEMENT AND&nbsp;ELEVATIONS<b>&nbsp;- WHAT IS THE ELEVATION OF THE BOTTOM OF THE SERVICE PANEL?</b></div><div><ol><li>FLOOD ZONE WHERE THE PROPOSED STRUCTURE WILL BE LOCATED MUST BE SPECIFIED (CCCO SEC 18-193 - FBC R322.2, R322.3 - DETERMINES REQUIREMENTS)</li><li>BFE &amp; DFE ELEVATIONS MUST BE STATED AND SHOWN ON ELEVATION PAGES (CCCO SEC 18-193 - FBC R322.1, R322.1.4.1)</li><li>STATEMENT IS REQUIRED THAT ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS TO BE AT OR ABOVE DFE (CCCO SEC 18-193 - FBC R322.1.6, FEMA P-348, PAGES 3-8)&nbsp;</li><li>ALL MATERIAL BELOW DFE MUST BE FLOOD RESISTANT AND CONFORM TO THE PROVISIONS OF FEMA TB-2(CCCO SEC 18-193 - FBC R322.1.8)</li></ol><div><b><u>ELECTRIC DENIED:</u></b></div></div></div><div>FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - ELECTRIC MUST MEET BFE: 10.0', EXISTING GRADE APPROX: 4.0' - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) - MISSING ALL FLOOD HAZARD INFORMATION - MISSING ELECTRIC STATEMENT AND ELEVATIONS - WHAT IS THE ELEVATION OF THE BOTTOM OF THE SERVICE PANEL?</div><div>1. FLOOD ZONE WHERE THE PROPOSED STRUCTURE WILL BE LOCATED MUST BE SPECIFIED (CCCO SEC 18-193 - FBC R322.2, R322.3 - DETERMINES REQUIREMENTS)</div><div>2. BFE &amp; DFE ELEVATIONS MUST BE STATED AND SHOWN ON ELEVATION PAGES (CCCO SEC 18-193 - FBC R322.1, R322.1.4.1)</div><div>3. STATEMENT IS REQUIRED THAT ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS TO BE AT OR ABOVE DFE (CCCO SEC 18-193 - FBC R322.1.6, FEMA P-348, PAGES 3-8)&nbsp;</div><div>4. ALL MATERIAL BELOW DFE MUST BE FLOOD RESISTANT AND CONFORM TO THE PROVISIONS OF FEMA TB-2(CCCO SEC 18-193 - FBC R322.1.8)</div>
Additional Information

04-29-2025PERMIT REVIEW COMMENT
<b><u>FLOOD DENIED:</u></b><div><div>FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - ELECTRIC MUST MEET BFE: 10.0', EXISTING GRADE APPROX: 4.0' - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) - MISSING ALL FLOOD HAZARD INFORMATION - MISSING ELECTRIC STATEMENT AND&nbsp;ELEVATIONS<b>&nbsp;- WHAT IS THE ELEVATION OF THE BOTTOM OF THE SERVICE PANEL?</b></div><div><ol><li>FLOOD ZONE WHERE THE PROPOSED STRUCTURE WILL BE LOCATED MUST BE SPECIFIED (CCCO SEC 18-193 - FBC R322.2, R322.3 - DETERMINES REQUIREMENTS)</li><li>BFE &amp; DFE ELEVATIONS MUST BE STATED AND SHOWN ON ELEVATION PAGES (CCCO SEC 18-193 - FBC R322.1, R322.1.4.1)</li><li>STATEMENT IS REQUIRED THAT ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS TO BE AT OR ABOVE DFE (CCCO SEC 18-193 - FBC R322.1.6, FEMA P-348, PAGES 3-8)&nbsp;</li><li>ALL MATERIAL BELOW DFE MUST BE FLOOD RESISTANT AND CONFORM TO THE PROVISIONS OF FEMA TB-2(CCCO SEC 18-193 - FBC R322.1.8)</li></ol><div><b><u>ELECTRIC DENIED:</u></b></div></div></div><div>FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - ELECTRIC MUST MEET BFE: 10.0', EXISTING GRADE APPROX: 4.0' - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%) - MISSING ALL FLOOD HAZARD INFORMATION - MISSING ELECTRIC STATEMENT AND ELEVATIONS - WHAT IS THE ELEVATION OF THE BOTTOM OF THE SERVICE PANEL?</div><div>1. FLOOD ZONE WHERE THE PROPOSED STRUCTURE WILL BE LOCATED MUST BE SPECIFIED (CCCO SEC 18-193 - FBC R322.2, R322.3 - DETERMINES REQUIREMENTS)</div><div>2. BFE &amp; DFE ELEVATIONS MUST BE STATED AND SHOWN ON ELEVATION PAGES (CCCO SEC 18-193 - FBC R322.1, R322.1.4.1)</div><div>3. STATEMENT IS REQUIRED THAT ALL MECHANICAL, ELECTRICAL, AND PLUMBING EQUIPMENT IS TO BE AT OR ABOVE DFE (CCCO SEC 18-193 - FBC R322.1.6, FEMA P-348, PAGES 3-8)&nbsp;</div><div>4. ALL MATERIAL BELOW DFE MUST BE FLOOD RESISTANT AND CONFORM TO THE PROVISIONS OF FEMA TB-2(CCCO SEC 18-193 - FBC R322.1.8)</div>

Review Distribution Approved
| Assigned to Reviewer: Salena Berg salena.berg@citrusbocc.com |
Flood Review Approved
FLOOD ZONE: AE - BFE: 12.0', DFE: 13.0' (PANEL: 12017C0186E, EFFECTIVE: 01/15/2021 - 120063) - STRUCTURE LOCATED IN ZONE: AE - NEW ELECTRICAL - CONTROL BOX BELOW DFE TO UTILIZE NEMA 6 ENCLOSURE - PRE-FIRM STRUCTURE - ELEVATION VERIFICATION AT FINAL INSPCT - NOT A SUBSTANTIAL IMPROVEMENT, (BUILDING VALUE: $407,752.80, PROJECT VALUE: $2,006.00, IMPROVEMENT: 0.49%)&nbsp;
Electrical Plan Review Approved
| Assigned to Reviewer: Mark Hammer mark.hammer@citrusbocc.com |
Review Consolidation Approved
| Assigned to Reviewer: Salena Berg salena.berg@citrusbocc.com |
Pre Permit Issuance Review Add Fees
| Assigned to Reviewer: Salena Berg salena.berg@citrusbocc.com |
Pre Permit Issuance Review Approved
| Assigned to Reviewer: Salena Berg salena.berg@citrusbocc.com |

Conditions

Inspections
Final Electric Inspection (#1)Scheduled For: 06-19-2025Is Assigned Passed on 06-19-2025
| Assigned to Inspector: Elizabeth BrownMcWatters |
Final Power Release (#1)Scheduled For: 06-19-2025Is Assigned Closed on 06-20-2025
BLD202505958 Owner Name: SAMUELSON RANDY A AND SAMUELSON MARCIA Inspection Passed on: 6/19/2025
Pre Power Release (#1)Scheduled For: 06-19-2025Is Assigned Confirmed on 06-19-2025
BLD202505958 Owner Name: SAMUELSON RANDY A AND SAMUELSON MARCIA