RECONNECTION OF EXISTING SERVICE TO VACANT RESIDENCE * INSPECTOR MUST CHECK FOR EVIDENCE OF TAMPERING AND/OR ANY REPAIRS THAT MAY BE NEEDED PRIOR TO ANY APPROVAL FOR RELEASE OF POWER OR ENERGIZING STRUCTURE IF ANY REPAIRS ARE TO BE DONE THIS APPLICATION WILL BE CLOSED AND A NEW ELECTRICAL PERMIT WILL BE REQUIRED* NOC N/A *
Other APPLICANT
Licensed Contact Primary APPLICANT FOR POWER RELEASE
Property Owner DAVID O & LAURA K VORE REEVES 7511 CHASSAHOWITZKA ST HOMOSASSA, FL 34448
Parent 199302476 Building History Added On: 11-05-1999 Status: Closed
PROOF OF OWNERSHIP NEEDED APPROVED on 04-29-2015 P/A
04-30-2015REINSPECTION REQUIRED 1. suspect 200 amp main brkr in exterior panel may not be viable 2.identify neutral conductors WHITE at all accessible points 3.id all grounds GREEN 4.close 4 ---1/2"k/o's bottom of pnl 5. missing 2 brkr blanks 6.water piping at well brkn
05-01-2015REINSPECTION REQUIRED 1. missing locknut and bonding bushing on mtl nipple between mtr can and panel nec 250 2. nec 250-need to add 2nd =ground rod -min 6' from 1st one 3.remove paralleled grounding electrode conductor from pnl to meter 4.id grounds GREEN
05-01-2015OTHER 5.nec 250.94-missing intersystem bonding bar 6.the ONLY brkrs that will fit into a Homeline panel are Homeline ...see cutler hammer and ITE installed--bottom rt brkr is correct one.........