PERMIT SEARCH PORTAL
Details

Identification

Permit Number
201504412
Type
BPEL - Electrical Type Permits
Added On
04-29-2015 11:37 AM
Declared Value
$50.00


Status (Closed)

Expires On
10-26-2015
Issued On
04-29-2015
Final On
03-16-2016
Certified On


Description of Work

RECONNECTION OF EXISTING SERVICE TO VACANT RESIDENCE * INSPECTOR MUST CHECK FOR EVIDENCE OF TAMPERING AND/OR ANY REPAIRS THAT MAY BE NEEDED PRIOR TO ANY APPROVAL FOR RELEASE OF POWER OR ENERGIZING STRUCTURE IF ANY REPAIRS ARE TO BE DONE THIS APPLICATION WILL BE CLOSED AND A NEW ELECTRICAL PERMIT WILL BE REQUIRED* NOC N/A *



Site Information

Primary Parcel (ID 1819300000220000174)
HIGH RIDGE ESTS UNREC SUB W1/2 OF W1/2 OF LT 17: W1/2 OF W1/2 OF THE FOL DESCR LANDS: COM AT SE COR OF SE1/4 SEC 30-19-18, TH S 87 DEG 52M 13S W AL S LN OF SE1/4 350.02 FT, TH N 0 DEG 06M 26S W 234 FT TO POB, TH S 87 DEG 49M 47S W 524.5 FT, TH N 0 DEG 06M 26S W 183.99 FT, TH N 87 DEG 49M 47S E 524.5 FT, TH S 0 DEG 06M 26S E 183.99 FT TO POB, TOGETHER WITH EASE OF RECORD TITLE IN OR BK 1881 PG 1270 OR BK 2337 PG 360
HIGH RIDGE ESTATES
19
18
30
22000
0174

Other Linked
5145 W STARBURST LN HOMOSASSA, FL 34446


Contacts

Contacts

Other APPLICANT

Licensed Contact Primary APPLICANT FOR POWER RELEASE

Property Owner DAVID O & LAURA K VORE REEVES 7511 CHASSAHOWITZKA ST HOMOSASSA, FL 34448



Related

Building Permits

Parent 199302476 Building History 11-05-1999 Closed



Progress

Reviews
04-29-2015FINAL PROCESSING REVIEW Approved


Conditions

PROOF OF OWNERSHIP NEEDED APPROVED on 04-29-2015
P/A


Inspections
FINAL ELECTRIC (#1)Scheduled For: 04-30-2015Is Assigned Canceled on 05-01-2015
**CALL 352-464-2977 30 MINUTES PRIOR TO FOR ACCESS**PLEASE *** RESCHEDULED ***
Violations

04-30-2015REINSPECTION REQUIRED
1. suspect 200 amp main brkr in exterior panel may not be viable 2.identify neutral conductors WHITE at all accessible points 3.id all grounds GREEN 4.close 4 ---1/2"k/o's bottom of pnl 5. missing 2 brkr blanks 6.water piping at well brkn

FINAL ELECTRIC (#2)Scheduled For: 05-01-2015Is Assigned Failed on 05-01-2015
**CALL 352-464-2977 30 MINUTES PRIOR TO FOR ACCESS**PLEASE *** ATTENTION: THIS IS A ROLLED OVER/RESCHEDULED INSPECTION ***
Violations

05-01-2015REINSPECTION REQUIRED
1. missing locknut and bonding bushing on mtl nipple between mtr can and panel nec 250 2. nec 250-need to add 2nd =ground rod -min 6' from 1st one 3.remove paralleled grounding electrode conductor from pnl to meter 4.id grounds GREEN

05-01-2015OTHER
5.nec 250.94-missing intersystem bonding bar 6.the ONLY brkrs that will fit into a Homeline panel are Homeline ...see cutler hammer and ITE installed--bottom rt brkr is correct one.........

FINAL ELECTRIC (#3)Scheduled For: 05-04-2015Is Assigned Passed on 05-05-2015